Battery Runtime Calculator (Load Current)

Quick answer

This calculator computes how long a battery lasts under load: runtime = Ah/load A adjusted for efficiency, discharge rate, and low-voltage cutoff with real derating.

Figures are estimates from this calculator’s standard formula — adjust the inputs in the tool below for your exact number.

How Does the Battery Runtime Calculator Work?

t = Ah × η ÷ I

Naive runtime is capacity divided by current, but three real-world factors shave it: inverter/converter efficiency (85-95 percent), Peukert derating on lead-acid at high rates (up to 30 percent), and unusable capacity below the cutoff voltage. The calculator folds them in. Example: a 100 Ah AGM battery feeding a 20 A inverter load nominally runs 5 h; with Peukert 1.25 and 85 percent efficiency, expect about 3.6 h before the 10.5 V cutoff. Check the inverter floor: lead-acid banks cut off near 10.5 V for 12 V systems, stranding the bottom 20 percent of charge, while lithium BMS units cut at 10-11 V but deliver most of the label.

  1. 1

    Enter battery capacity

    Ah from the label.

  2. 2

    Enter load current

    Average amps drawn.

  3. 3

    Set efficiency

    Or accept the realistic default.

Use Cases

Predicting UPS hold time for servers and network racks

Sizing trolling motor and RV house batteries

Planning backup power for CPAP and medical devices

Common Mistakes

  • Using label Ah at a discharge rate the battery cannot sustain

  • Ignoring the inverter's own idle draw, which matters on light loads

  • Treating lithium and lead-acid derating as identical

FAQs

How long will a 100Ah battery run a 400W inverter load?

At 12 V that is 33.3 A: naive 3 h. For lead-acid apply Peukert (about 0.75) and 85 percent inverter efficiency: about 1.9-2.2 h. Lithium delivers closer to 2.5 h because it shrugs off rate derating.

What is the Peukert effect?

Lead-acid capacity shrinks as discharge speeds up: a 100 Ah battery rated at 20-hour rate delivers perhaps 70 Ah at 2-hour rate. Exponent 1.2-1.3 for AGM, 1.1-1.15 for lithium-free LFP... effectively none.

Why does runtime drop in cold weather?

Below 0 C lead-acid can lose 30-50 percent of usable capacity and internal resistance rises; lithium loses 10-20 percent and recovers when warmed. Cold cranking failures are mostly this effect, not a dead battery.

How long will my UPS run the router and modem?

A typical 1500 VA UPS with 9 Ah internals feeding 30 W of network gear lasts about 25-30 minutes: 9 x 12 x 0.85/30 = 3.06 Ah-hours of usable 12 V energy. Adding a NAS drains it three times faster.